The following information may have errors; It is not permissible to be read by anyone who has ever met a lawyer. Use is confined to Engineers with more than 370 course hours of electronic engineering for theoretical studies. All content entered becomes and is (C)2007 Transtronics, Inc. the property of Transtronics, Inc. Rest assured that your contributions won't be sold and will be publicly available.
ph +1(785) 841 3089 Email inform@xtronics

Mass Flow by square root extraction

From Transwiki

Jump to: navigation, search

Measuring the flow of fluids with an orifice plate

Sometimes we want to measure the flow of a material that isn't happy going through an impeller (or we might want to avoid having to maintain the shaft seal). One way to accomplish this is with a differential pressure transducer that looks at the difference of pressure across an orifice plate.

We can get volume or mass flow using the following equation

m_f = \rho_1\;Q_1 = C\;Y\;A\;\sqrt{2\;\rho_1\;(P_1-P_2)}


where


Q1 = upstream volumetric flow, m³/s
mf = mass flow rate at any point, kg/s
C = orifice flow coefficient
Y = expansion factor
A = cross-sectional area of orifice, m²
P1 = upstream pressure, Pa   kg/(m ·s)
P2 = downstream pressure, Pa   kg/(m ·s)
ρ1 = upstream fluid density, kg/m³

In practice C\;Y\;A_2\; become a lumped constant along with any unit scaling- Let's call this constant k\; then

m_f = k\;\sqrt{2\;\rho_1\;(P_1-P_2)}

The flow is a constant times the square root of a constant times the pressure difference.

Panel meters often can figure out k\; and ρ1 by looking at two known flow rates.