The following information may have errors; It is not permissible to be read by anyone who has ever met a lawyer. Use should also be confined to Engineers with more than 370 course hours of electronic engineering and should only be used for theoretical studies. All content entered becomes and is (C)2007 Transtronics, Inc. the property of Transtronics, Inc. Rest assured that your contributions won't be sold and will be publicly available.
T2 to V2000 Conversion
From Transwiki
Contents |
[edit] T2 Series PLCs to V2000 Series PLCs –Equivalent Items
Most of these are exactly equivalent - but there can be some with slight differences - most often they will be more capable.
Most peopl transitioning will want to continue to use the same programming software - and it is possible with a little fiddling to move a T2 program over to a V2000 system if you use the T2E processor - see GPU612E*S
[edit] Equivalent Card numbers
[edit] Output Cards
- EX10-MRO61 Similar look at GRO663**S Relay Output Module, 12 points (use 16 point GRO663**S).
- EX10-MRO62 use GRO662S*S Relay Output Module, 8 points (isolated), 240 Vac/24Vdc (max.), 2 A/point
- EX10-MAC61 use GAC663**S AC Output Module, 12 points, 100 to 240 Vac, 1 A/point
- EX10-MDO31 use GDO633**S DC Output Module, 16 points, 5 to 24 Vdc, 1 A/point, Sink (source load)
- EX10-MDO32 use GDO634**S DC Output Module, 32 points, 5 to 24 Vdc, (cable connector is different).
- TDO233P-S use GDO633P*S DC Output Module, 16 points, 5 to 24 Vdc, 1 A/point, Source
- TDO235--S use GDO635**S DC Output Module, 64 points, 5 to 24 Vdc, 0.1 A/point, Sink
[edit] Input Cards
- EX10-MDI31 use GDI633**S DC Input Module, 16 points, 12 to 24 Vdc
- EX10-MDI32 use GDI634**S DC Input Module, 32 points, 24 Vdc (cable connector is different).
- EX10-MIN51 use GIN653**S AC Input Module, 16 points, 100 to 120 Vac
- EX10-MIN61 use GIN663**S AC Input Module, 16 points, 200 to 240 Vac
- TDI235--S use GDI635**S DC Input Module, 64 points, 24 Vdc
- TDI235H-S use GDI635H*S DC Input Module, High-speed, 64 points, 24 Vdc.
- EX10-MPI21 Similar look at GPI632**S Pulse Input Module, 1 channel,
[edit] Analog Input Cards
- EX10-MAI21 use GAD624L*S Analog Input Module, 4 channels, 1-5 Vdc / 4-20 mA, 8-bit
- EX10-MAI22 use GAD624**S Analog Input Module, 4 channels, 1-5 Vdc / 4-20 mA, 12-bit
- EX10-MAI31 use GAD634L*S Analog Input Module, 4 channels, 0-10 Vdc input, 8-bit
- EX10-MAI32 use GAD674**S Analog Input Module, 4 channels, ± 10 Vdc input, 12-bit
- TAD268--S use GAD628S*S Analog Input Module, 8 channels, 0-5 V, 0-20 mA, 12 bit break
- TAD268--S use GAD638S*S Analog Input Module, 8 channels, ± 10 V input, 12-bit break
- TAD268--S use GAD668**S Analog Input Module, 8 channels, 0-5 V, 0-20 mA, ± 10 V, 16-bit
[edit] Analog Output Cards
- EX10-MAO22 use GDA622**S Analog Output Module, 2 channels, 1-5Vdc, 4-20 mA output, 12-bit
- EX10-MAO31 use GDA622L*S Analog Output Module, 2 channels, 1-5 Vdc / 4-20 mA, 8-bit
- EX10-MAO32 use GDA672**S Analog Output Module, 2 channels, ±10Vdc, 12-bit
- TDA264--S use GDA664**S Analog Output Module, 4 channels, 0-5 V, 0-20 mA, ± 10 V, 16-bit
[edit] Tosline Cards
- FMS211AM use GUN611**S TOSLINE-F10, Single bus, twisted paired-cable, Master station
- FRS211AM use GUN612**S TOSLINE-F10, Single bus, twisted paired-cable, Slave station
- SSN221-MS use GSN621**S TOSLINE-S20, Single bus, coaxial cable, S2E/S2 systems only.
- SSN222AMS use GSN622**S TOSLINE-S20, Single bus, optical cable, S2E/S2 systems only.
[edit] Networking
- TCF211--S use GCF611**S Communications Module, 1 ch, RS232C, ASCII.
- TDN211A-S use GDN611A*S DeviceNet Scanner Module
- TFL212**S use GFL612**S FA Network, FL-net Station Module, 10 Mbps, Ver 2.0
- TMC211--S use GMC612**S Position Control Module, 2 Axis, up to 200 kpps.
- EX10-MMC11 Similar look at GMC612**S Position Control, 1 Axis.
- TPI232--S use GPI632**S Pulse Input Module, 2 channels, up to 50 kpps, 5/12/24 V input, 24-bit counter
- TPI272--S use GPI672**S Pulse Input Module, 2 channels, up to 50 kpps, RS422 input, 24-bit counter
- TRO263--S use GRO663**S Relay Output Module, 16 points, 240 Vac/24 Vdc (max.), 2 A/point
- TTC218--S use GTC618**S Thermocouple Input Module, 8 channels, E, J, K, 16-bit
- EX10-ABP1 use GSP600*AS Module, Blank (not required for V2000 Series)
- EX25SER6 use GBT611**S Battery
[edit] Cables
- EX10-CAR3 use GCS6R3*CS Expansion Cable, 0.3 m length
- EX10-CAR5 use GCS6R5*CS Expansion Cable, 0.5 m length
- EX10-CAR7 use GCS6R7*CS Expansion Cable, 0.7 m length
- TCS2RF-CS use GCS6*1*CS Expansion Cable, 1.2 m length
[edit] Racks
- TBU218--S use GBU668**S Base Rack for S2E, 8 I/O Slots/ Expansion Rack for S2T/S2, 8 I/O Slots.
- TBU268--S use GBU666**S Base Rack for S2E, 5 I/O Slots/ Expansion Rack for S2T/S2, 6 I/O Slots.
- TBU266--S use GBU664**S Base Rack for S2E, 3 I/O Slots/ Expansion Rack for S2T/S2, 4 I/O Slots.
- TBU228N-S use GBU643E*S Base Rack for S2T/S2, 8 Slots (Up to 5 station bus slots). Not for S2E.
[edit] Power Supplies
- EX10-MPS31 use GPS632**S 24 Vdc power supply, For Main/Expansion Racks.
- TPS261--S use GPS693**S 120/240 Vac power supply, For Main/Expansion Racks, 24Vdc Service PS
- Or use GPS652**S 100-110 Vdc power supply, For Main/Expansion Racks.
[edit] CPUs
- TPU234E-S use GPU612E*S Sequence Control Module (S2E), User program capacity 32 kSteps, T-series Instruction Set, Uses T-PDS Programming Software.
- TCM231EAS ----- Included on use GPU612E-S.
- TPU215N-S use GBU612E*S Sequence Control Module (S2E), User program capacity 32 kSteps, T-series Instruction Set, Uses T-PDS Programming Software
- TPU235N-S use GBU662T*S Sequence Control Module (S2T), User program capacity 32 kSteps, T-series Instruction Set, Uses T-PDS Programming Software
- Or use GEN651A*S Ethernet Module, Single bus, 100 Base-TX.
- TPU245N-S use GBU662T*S Sequence Control Module (S2T), User program capacity 32 kSteps, T-series Instruction Set, Uses T-PDS Programming Software
- Or use GSN627**S TOSLINE-S20LP, Double loop optical cable, S2T only.
- Or use GEN651A*S Ethernet Module, Single bus, 100 Base-TX.